Wednesday, 13 August 2014

Burden Understanding Of Current Transformer.

BURDEN
The term of burden is always raised on the instrumentation transformers, both current transformer and voltage transformer. Sometime, term of burden is also equated with the term of load. Since the understanding of burden are very important and significant to an accuracy class of current transformer and voltage transformer, we try to present it in a comprehensive manner to assist practitioners in the field of medium voltage control to have better understanding of the burden.
As started, we will explain the meaning of burden for current transformer.

BURDEN DEFINITION
Definition of burden base on IEC 60044-1 standard.
The impedance of the secondary circuit in ohms and power-factor.
The burden is usually expressed as the apparent power in voltamperes absorbed at a specified power-factor and at the rated secondary current.

Thus, a burden can be expressed in two ways, namely:
Firstly, as the total impedance of the secondary circuit in Ohms. This definition is commonly used in ANSI / IEEE standard.
The following table of burden base on ANSI/IEEE Standard.


Below are sample of Metering Current transformer technical spec base on ANSI/IEEE standard.

0.3B0.2
0.3 is indicating class accuracy of current transformer, with limit error between +/- 0.3%  and B0.2 is indicating a burden, with impedance value of 0.2 Ohm.

0.6B0.9
0.6 is indicating class accuracy of current transformer, with limit error between +/- 0.6%  and B0.9 is indicating a burden, with impedance value of 0.9 Ohm.

Secondly, burden can be expressed as form of apparent power VA at certain power factor in the rated secondary current.
This definition commonly used in IED60044-1 standard. In this standard, manufacture has to perform class accuracy using burden at certain value with power factor 0.8 lagging as shown of below statement:

For testing purposes when determining current error and phase displacement, the burden shall have a power-factor of 0.8 inductive except that, where the burden is less than 5 VA, a power factor of 1.0 is permissible.

Note:
Burden and accuracy class is 2 things are interrelated, so it is always defined simultaneously. The value of error ratio and phase displacement will shift from the pre-defined value that is used when the burden is larger or smaller than a predetermined limit burden.

As we know, the definition of the secondary circuit is a circuit which is connected to the secondary coil of the current transformer. Secondary circuit may include a cable, or measuring and protection equipment.
If illustrated in graphic form, the understanding of burden is shown in the below figure.



Thus, burden of current transformer are includes all components connected to the secondary coil of the current transformer such as meters or protective equipment, connectors, cable, indicator lights, and so forth. In the above example, the burden including the connecting cable impedance and measuring or protection equipment.

Since the resistance of connecting cable between the current transformer’ secondary terminal and measuring equipment or protective equipment greatly impact the performance of a current transformer, then some of the following should be noted.
  • When measuring or protective equipment is located far away from the secondary terminal of current transformer, The secondary current should be used lower value, such as 1 ampere. Using a current transformer with a 5 ampere output rating for measuring devices located far away from the secondary terminals, will lead to a bigger  VA that is absorbed by the cable.
  • To ensure accuracy in the range of values ​​corresponding to the results of the manufacturer, the value of the burden should be in the range of 25% to 100% of rated burden (for Current Transformer with standard IEC60044-1) or in the value of rated burden(ANSI / IEEE C57. 13).
  • Use of a larger or smaller burden than the burden identifier (rated burden), will lead to the increasing of error ratio (ratio error and phase shift).
  • Use of burden that is not suitable, it will also result a shifted  value of FS or ALF, which can cause damage to the measuring equipment or the protective current transformer will easily saturated.

1 comment:

  1. Betway Casino – Welcome Bonus of 200 Free Spins
    Betway is one 출장안마 of the best names when it comes to https://octcasino.com/ online poormansguidetocasinogambling casino jancasino in the world. Their games are kadangpintar varied, generous, and generous with

    ReplyDelete